73VR2100 - Paperless Recorder with built-in I/O
Built-in universal input modules.
Universal input DC, Thermocouple, RTD
- Independent input type and range selectable for each channel
- 100 msec. storing rate up to 6 point
- 2, 4, 6, 8, 10 or 12 points
- Real time trending and recording on the PC Recorder software MSR via Ethernet
| QUICK SETUP |
|---|
|
Intuitive “Help View” screen for easy user setup and use. ![]() |
| INPUT TYPE | |
|---|---|
| DC Voltage | Input resistance: 900kΩ minimum (Excluding the case in which, with range setting other than ±12V, ±6V or ±3V, a voltage exceeding ±1.3V is applied.) |
| Input range: ±60mV, ±125mV, ±250mV, ±500mV, ±1000mV, ±3V, ±6V, ±12V | |
| DC Current | 4-20mA, use optional REM3-250 resistor module |
| Thermocouple | Input range: (PR), K (CA), E (CRC), F (IC), T (CC), B (RH), R, S, C (WRe 5-26), N, U, L, P (Platinel II) |
| Burnout sensing: • Upscale: ≤130nA • Downscale: ≤220nA • No burnout: ≤10nA |
|
| RTD (3-wire) | Input range: Pt 100 (JIS ’89), Pt 100 (JIS ’97, IEC), Pt 200, Pt 300, Pt 400, Pt 500, Pt 1000, Pt 50Ω (JIS ’• ;81), JPt 100 (JIS ’89), Ni 100, Ni 120, Ni 508.4Ω, Ni-Fe 604, Cu 10 @25°C |
| Burnout sensing: • Upscale or Downscale: ≤130nA |
|
| Allowable leadwire resistance: 20Ω per wire | |
| SPECIFICATIONS | ||
|---|---|---|
| Number of input channels | 2, 4, 6, 8, 10 or 12 | |
| Function pen points | 12 | |
| Storing rate (high speed mode) | 100 msec. | |
| Storing rate (normal mode) | 500 msec., 1, 2, 5, 10 seconds, 1minute, 10 minutes | |
| Input types | Universal input (DC mV and voltage, thermocouple, 3-wire RTD) | |
| Trigger input | Dry contact x 1 | |
| Alarm/Run output | Relay contact x 1 | |
| Weight | 2.4 kg (5.3 lbs) | |
| Display | Display device | 5.5-inch TFT LCD |
| Display colors | 256 | |
| Resolution | 320 x 240 pixels | |
| Ethernet | 10BASE-T / 100BASE-TX automatically switched; Conforms to IEEE802 (10BASE-T) or IEEE802.3 (100BASE-TX) |
|
| Degree of protection | IP65 (applicable to the front panel of with the cover closed when a single unit is mounted according to the specified panel cutout) |
|