73VR3100 - Paperless Recorder with selectable built-in I/O
Selectable input modules.
Flexible I/O capability using the R3 series modules.
Compatible with various open networks.
- Up to four R3 Series I/O modules can be selected (Max. 64 inputs).
- By replacing one of the I/O modules with Network Module for the R3 Series, the 73VR3100 can directly communicate to major PLC via Modbus, Ethernet (Modbus/TCP), DeviceNet, PROFIBUS-DP, CC-Link, LONWORKS, T-Link and FL-net.
- 20 msec. storing rate with the combination of 8 analog and 8 discrete inputs.
- Real time trending and recording on the PC Recorder software MSR via Ethernet.
Open network module installed,
using 73VR3100 as remote I/O with local display and recording function.
Direct operation and configuration from PLC

- The host PLC can control the 73VR3100 via built-in gateway module to start / stop recording, enter comments and set displays. *1
- Data sent from PLC can be displayed and record. *2
*1. In"Remote" mode, local control at the 73VR3100 is locked.
*2. Storing rate 20 msec. is not selectable.
Gateway Interface Modules *3
Network | Model | Function |
---|---|---|
CC-linK | R3-GC1 | Ver.2.00 |
DeviceNet | R3-GD1 | Analog 64ch |
Modbus / TCP | R3-GE1 | Ethernet |
Modlus | R3-GM1 | RS-485 |
FL-net | R3-GE1 | OPCN-2 |
*3. The number of gateway module vary by its settings
SPECIFICATIONS | ||
---|---|---|
Number of input channels | 4 through 64 | |
Function pen points | 16, 64 | |
Storing rate (high speed mode) | 20 msec., 100 msec. | |
Storing rate (normal mode) | 500 msec., 1, 2, 5, 10 seconds, 1minute, 10 minutes | |
Input types | R3 series I/O modules (DC voltage, DC current, Thermocouple, RTD, AC voltage, AC current, Encoder, Totalized pulse, Di/o) | |
Trigger input | Max. 64 (depending on input modules types) | |
Alarm/Run output | Max. 32 (depending on input modules types) | |
Weight | 2.3 kg (5.1 lbs) except I/O modules | |
Display | Display device | 5.5-inch TFT LCD |
Display colors | 256 | |
Resolution | 320 x 240 pixels | |
Ethernet | 10BASE-T / 100BASE-TX automatically switched; Conforms to IEEE802 (10BASE-T) or IEEE802.3 (100BASE-TX) |
|
Degree of protection | IP65 (applicable to the front panel of with the cover closed when a single unit is mounted according to the specified panel cutout) |