5725
Programmable frequency indicator
- Measures NPN, PNP, Contact, NAMUR, S0, Tacho and TTL sensors
- Programmable frequency input span of 0.001 Hz to 50 kHz
- The 5725D has two SPDT relays and one analog output
- Easy to read 4-digit, 14-segment LED display with scrolling help text
- Universally powered by 21.5…253 VAC or 19.2… 300 VDC
Manuals : 
Data sheet : 
- Application- The 5725 measures, scales, and displays frequency signals found in many process speed and flow rate applications.
- The indicator can measure the period of the frequency, useful for displaying the elapsed time between events.
- The 5725D has two SPDT setpoint contacts and a 0/4...20 mA output for process control.
- The installed display provides IP65 environmental sealing, and additional protection is provided by the optional 8335 splash proof cover.
 - Technical characteristics- 4-digit display with 13.8 mm high, 14-segment LED digits and adjustable decimal point.
- Indicator is scalable from -1999 to 9999.
- Scrolling help text makes programming easy.
- Customizable trigger levels allow measurement of nearly any pulse sensor.
- Built-in excitation source for measuring NPN, PNP, NAMUR and S0 sensors.
- Fast response time of 1 cycle + 100 ms, and excellent accuracy of better than 0.05% of selected range.
- The analog output current on the 5725D can be dampened from 0.1 to 60 seconds, and can handle up to 800 Ohms loop load.
- The 5725 meets NAMUR NE21 recommendations for high performance in harsh EMC environments.
- High 2.3 kVAC galvanic isolation, and an excellent signal/noise ratio of > 60dB.
 - Mounting / installation / programming- Easy to mount 1/8 DIN (48x96 mm) panel meter with IP65 (type 4X) sealing.
- Approved for marine applications.
- Fully push-button programmable.
- Password-protected.
 
- Environmental Conditions- Specifications range - -20°C to +60°C - Storage temperature - -40°C to +85°C - Calibration temperature - 20...28°C - Relative humidity - < 95% RH (non-cond.) - Protection degree - IP20 - Protection degree (mounted in panel) - IP65 / Type 4X, UL50E - Installation in - Pollution degree 2 & measurement / overvoltage cat. II - Mechanical specifications- Dimensions (HxWxD) - 48 x 96 x 120 mm - Cut out dimensions - 44.5 x 91.5 mm - Weight approx. - 230 g - Wire size, pin 11-12 & 41-44, max. - 1 x 1.5 mm2/ AWG 30...16 stranded wire - Wire size, others, max. - 1 x 2.5 mm2/ AWG 30...12 stranded wire - Terminal connection - Spring-cage - Vibration - IEC 60068-2-6 : 2007 - Vibration: 2...25 Hz - ±1.6 mm - Vibration: 25...100 Hz - ±4 g - Common specifications- Supply voltage, universal - 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC - Max. power consumption - < 2.8 W (5725A) < 3.6 W (5725D) - Isolation voltage, test / working - 2.3 kVAC / 250 VAC - Signal / noise ratio - > 60 dB - Accuracy - Better than 0.05% of selected range - Response time (0...90%, 100...10%) - < 1 period + 100 ms - EMC immunity influence - < ±0.5% of span - Extended EMC immunity: NAMUR NE 21, A criterion, burst - < ±1% of span - Input specifications- Frequency range, f/I conversion function - 0.001 Hz to 50 kHz - Low cut-off frequency - 0.0009 Hz (default value) - Max. frequency, with input filter ON - 50 Hz - Time range, period time function - 999.9 s to 20 μs - Low cut off period time (time-out) - 1111 s - Min. period time with input filter ON - 20 ms - Input types - NAMUR acc. to EN 60947-5-6 Tacho 
 NPN / PNP
 TTL
 S0 acc. to DIN 43864
 Special voltage
 Special current- Output specifications- Display readout - -1999...9999 (4 digits) - Decimal point - Programmable - Digit height - 13.8 mm - Display updating. - 2.2 times / s - Input outside input range is indicated by - Explanatory text - Programmable current ranges - 0...20 / 4...20 / 20...0 and 20...4 mA - Load (max.) - 20 mA/800 Ω/16 VDC - Load stability, current output - ≤0.01% of span / 100 Ω - Current limit - ≤ 28 mA - Sensor error indication, current output - 0 / 3.5 / 23 mA / none - Output limitation, on 4...20 and 20...4 mA signals - 3.8...20.5 mA - Output limitation, on 0...20 and 20...0 mA signals - 0...20.5 mA - Relay output: Relay functions - Setpoint - Hysteresis, in % / display counts - 0...100% / 0...9999 - ON and OFF delay - 0...3600 s - Power On delay - 0...60 s - Sensor error reaction - Break / Make / Hold - Max. voltage - 250 VRMS - Max. current - 2 AAC - Max. AC power - 500 VA - Max. load at 24 VDC - 1 A - Approvals- EMC - EN 61326-1 - LVD 2006/95/EC - EN 61010-1 - EAC TR-CU 020/2011 - EN 61326-1 - DNV Marine - Stand. f. Certific. No. 2.4 - UL - UL 508 


 
  
 