5725
Programmable frequency indicator
- Measures NPN, PNP, Contact, NAMUR, S0, Tacho and TTL sensors
- Programmable frequency input span of 0.001 Hz to 50 kHz
- The 5725D has two SPDT relays and one analog output
- Easy to read 4-digit, 14-segment LED display with scrolling help text
- Universally powered by 21.5…253 VAC or 19.2… 300 VDC
Manuals : 
Data sheet : 
Application
- The 5725 measures, scales, and displays frequency signals found in many process speed and flow rate applications.
- The indicator can measure the period of the frequency, useful for displaying the elapsed time between events.
- The 5725D has two SPDT setpoint contacts and a 0/4...20 mA output for process control.
- The installed display provides IP65 environmental sealing, and additional protection is provided by the optional 8335 splash proof cover.
Technical characteristics
- 4-digit display with 13.8 mm high, 14-segment LED digits and adjustable decimal point.
- Indicator is scalable from -1999 to 9999.
- Scrolling help text makes programming easy.
- Customizable trigger levels allow measurement of nearly any pulse sensor.
- Built-in excitation source for measuring NPN, PNP, NAMUR and S0 sensors.
- Fast response time of 1 cycle + 100 ms, and excellent accuracy of better than 0.05% of selected range.
- The analog output current on the 5725D can be dampened from 0.1 to 60 seconds, and can handle up to 800 Ohms loop load.
- The 5725 meets NAMUR NE21 recommendations for high performance in harsh EMC environments.
- High 2.3 kVAC galvanic isolation, and an excellent signal/noise ratio of > 60dB.
Mounting / installation / programming
- Easy to mount 1/8 DIN (48x96 mm) panel meter with IP65 (type 4X) sealing.
- Approved for marine applications.
- Fully push-button programmable.
- Password-protected.
Environmental Conditions
Specifications range -20°C to +60°C Storage temperature -40°C to +85°C Calibration temperature 20...28°C Relative humidity < 95% RH (non-cond.) Protection degree IP20 Protection degree (mounted in panel) IP65 / Type 4X, UL50E Installation in Pollution degree 2 & measurement / overvoltage cat. II Mechanical specifications
Dimensions (HxWxD) 48 x 96 x 120 mm Cut out dimensions 44.5 x 91.5 mm Weight approx. 230 g Wire size, pin 11-12 & 41-44, max. 1 x 1.5 mm2/ AWG 30...16 stranded wire Wire size, others, max. 1 x 2.5 mm2/ AWG 30...12 stranded wire Terminal connection Spring-cage Vibration IEC 60068-2-6 : 2007 Vibration: 2...25 Hz ±1.6 mm Vibration: 25...100 Hz ±4 g Common specifications
Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC Max. power consumption < 2.8 W (5725A) < 3.6 W (5725D) Isolation voltage, test / working 2.3 kVAC / 250 VAC Signal / noise ratio > 60 dB Accuracy Better than 0.05% of selected range Response time (0...90%, 100...10%) < 1 period + 100 ms EMC immunity influence < ±0.5% of span Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span Input specifications
Frequency range, f/I conversion function 0.001 Hz to 50 kHz Low cut-off frequency 0.0009 Hz (default value) Max. frequency, with input filter ON 50 Hz Time range, period time function 999.9 s to 20 μs Low cut off period time (time-out) 1111 s Min. period time with input filter ON 20 ms Input types NAMUR acc. to EN 60947-5-6 Tacho
NPN / PNP
TTL
S0 acc. to DIN 43864
Special voltage
Special currentOutput specifications
Display readout -1999...9999 (4 digits) Decimal point Programmable Digit height 13.8 mm Display updating. 2.2 times / s Input outside input range is indicated by Explanatory text Programmable current ranges 0...20 / 4...20 / 20...0 and 20...4 mA Load (max.) 20 mA/800 Ω/16 VDC Load stability, current output ≤0.01% of span / 100 Ω Current limit ≤ 28 mA Sensor error indication, current output 0 / 3.5 / 23 mA / none Output limitation, on 4...20 and 20...4 mA signals 3.8...20.5 mA Output limitation, on 0...20 and 20...0 mA signals 0...20.5 mA Relay output: Relay functions Setpoint Hysteresis, in % / display counts 0...100% / 0...9999 ON and OFF delay 0...3600 s Power On delay 0...60 s Sensor error reaction Break / Make / Hold Max. voltage 250 VRMS Max. current 2 AAC Max. AC power 500 VA Max. load at 24 VDC 1 A Approvals
EMC EN 61326-1 LVD 2006/95/EC EN 61010-1 EAC TR-CU 020/2011 EN 61326-1 DNV Marine Stand. f. Certific. No. 2.4 UL UL 508