3118
Bipolar isolated converter / splitter
- Conversion of voltage and current bipolar process signals to
 uni-/bipolar signals
- Multiple signal ranges are selectable via DIP-switches
- Splitter function: 1 signal in and 2 signals out
- Excellent accuracy, better than 0.05 % of selected range and high output load stability
Manuals : 
Data sheet : 
- Application- The 3118 is an isolating converter and splitter which can be used for signal conversion of standard bipolar analog process signals into two individual unipolar analog signals.
- The unit offers 4-port isolation and provides surge suppression and protects control systems from transients and noise.
- The 3118 also eliminates ground loops and can be used for measuring floating signals.
- Mounting of the 3118 can be in Safe area or in Zone 2 and Cl. 1 Div 2 area and is approved for marine applications.
- The analog output can be easily configured and programmed to be bipolar in the ranges ±10 mA and ±20 mA (*special setup).
 - Technical characteristics- Flexible 24 VDC (±30%) supply via power rail or connectors.
- Excellent conversion accuracy, better than 0.05% of selected range.
- A green front LED indicates operation status for the device.
- All terminals are protected against overvoltage and polarity error.
- Meeting the NAMUR NE21 recommendations, the 3118 ensures top measurement performance in harsh EMC environments.
- High galvanic isolation of 2.5 kVAC.
- Fast input to output response time < 7 ms / > 100 Hz – 10 Hz bandwidth damping possible via DIP-switch.
- Excellent signal/noise ratio > 60 dB.
 - Mounting / installation / programming- Easy configuration of factory calibrated measurement ranges via DIP-switches.
- A very low power consumption allows DIN rail mounting without the need for any air gap.
- Wide temperature operation range: -25...+70°C.
 
- Environmental Conditions- Specifications range - -25°C to +70°C - Storage temperature - -40°C to +85°C - Calibration temperature - 20...28°C - Relative humidity - < 95% RH (non-cond.) - Protection degree - IP20 - Installation in - Pollution degree 2 & measurement / overvoltage cat. II - Mechanical specifications- Dimensions (HxWxD) - 113 x 6.1 x 115 mm - Weight approx. - 70 g - DIN rail type - DIN EN 60715/35 mm - Wire size - 0.13 x 2.5 mm2 / AWG 26...12 stranded wire - Screw terminal torque - 0.5 Nm - Common specifications- Supply voltage - 16.8...31.2 VDC - Max. power consumption - 0.8 W - Internal consumption - 0.4 W (typ.) / 0.65 W (max.) - Isolation voltage, test - 2.5 kVAC - Isolation voltage, working - 300 VAC (reinforced) / 250 VAC (Zone 2, Div. 2) - MTBF, acc. to IEC 61709 (SN29500) - > 187 years - Signal / noise ratio - > 60 dB - Cut-off frequency (3 dB) - > 100 Hz or 10 Hz (selectable via DIP-switch) - Response time (0...90%, 100...10%) - < 7 ms or < 44 ms - Accuracy - < ±0.05% of span - Temperature coefficient - < ±0.01% of span / °C - EMC immunity influence - < ±0.5% of span - Extended EMC immunity: NAMUR NE 21, A criterion, burst - < ±1% of span - Input specifications- Current input: Programmable measurement ranges - ± 10 and ± 20 mA - Functional range, current input - -23...+23 mA - Input voltage drop - < 1 VDC @ 23 mA - Voltage input: Programmable ranges - ±5 and ±10 V - Functional range, voltage input - -11.5...+11.5 V - Input resistance, voltage input - ≥ 1 MΩ - Output specifications- Programmable current ranges - 0 / 4...20 mA - Functional range, current output - 0...23 mA - Load (max.) - 23 mA / 300 Ω / per ch. - Load stability, current output - ≤ 0.002% of span / 100 Ω - Current limit - ≤ 28 mA - Programmable voltage ranges - 0/1...5 and 0/2...10 V - Functional range, voltage output - 0...11.5 V - Load (min.) - > 10 kΩ - Bipolar wiring and programming set-up - ±10 and ± 20 mA - *of span - = of the presently selected range - Approvals- EMC - EN 61326-1 - LVD 2006/95/EC - EN 61010-1 - ATEX 2004/108/EC - KEMA 10ATEX0147 X - IECEx - KEM 10.0068X - FM - 3041043-C - EAC TR-CU 020/2011 - EN 61326-1 - DNV Marine - Stand. f. Certific. No. 2.4 - GL - V1-7-2 - UL - UL 61010-1 


 
  
 