- Advanced features- Programmable by way of detachable display front (4501), process calibration, signal simulation, password protection, error diagnostics and help text available in several languages.
 - Application- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with standard analog output.
- Galvanic separation of analog signals and measurement of floating signals.
- The 4114 is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
 - Technical characteristics- When 4114 is used with the 4501 display / programming front, all operational parameters can be modified to suit any application. As the 4114 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green / red front LED indicates normal operation and malfunction.
- Continuous check of vital stored data for safety reasons.
- 3-port 2.3 kVAC galvanic isolation.
 
- Environmental Conditions- Specifications range - -20°C to +60°C - Calibration temperature - 20...28°C - Relative humidity - < 95% RH (non-cond.) - Protection degree - IP20 - Mechanical specifications- Dimensions (HxWxD) - 109 x 23.5 x 104 mm - Dimensions (HxWxD) w/ 4501 / 4511 - 109 x 23.5 x 116 / 131 mm - Weight approx. - 145 g - Weight incl. 4501 / 4511 (approx.) - 160 g / 245 g - Wire size - 1 x 2.5 mm2 stranded wire - Screw terminal torque - 0.5 Nm - Vibration: 2...13.2 Hz - ±1 mm - Vibration: 13.2...100 Hz - ±0.7 g - Common specifications- Supply voltage, universal - 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC - Fuse - 400 mA SB / 250 VAC - Max. power consumption - ≤ 2.0 W - Isolation voltage, test / working - 2.3 kVAC / 250 VAC - Communications interface - Communication enabler 4511 / Programming front 4501 - Signal / noise ratio - Min. 60 dB (0...100 kHz) - Response time (0...90%, 100...10%): Temperature input - ≤ 1 s - Response time (0...90%, 100...10%): mA / V input - ≤ 400 ms - Auxiliary supplies: 2-wire supply (terminal 44...43) - 25...16 VDC / 0...20 mA - Accuracy - Better than 0.1% of selected range - EMC immunity influence - < ±0.5% of span - Extended EMC immunity: NAMUR NE 21, A criterion, burst - < ±1% of span - Input specifications- RTD input - Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000 Ni50, Ni100, Ni120, Ni1000, Cu10, Cu20, Cu50, Cu100 Linear resistance 
 Potentiometer- Cable resistance per wire (max.), RTD - 50 Ω - Sensor current, RTD - Nom. 0.2 mA - Effect of sensor cable resistance (3-/4-wire), RTD - < 0.002 Ω / Ω - Sensor error detection, RTD - Yes - Short circuit detection, RTD - < 15 Ω - TC input: Thermocouple type - B, E, J, K, L, N, R, S, T, U, W3, W5, LR - Cold junction compensation (CJC) via ext. sensor in connector 5910 - 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C - CJC via internally mounted sensor - ±(2.0°C + 0.4°C * Δt) - Δt = - Internal temperature-ambient temperature - Sensor error detection, TC - Yes - Sensor error current: When detecting / else - Nom. 2 μA / 0 μA - Current input: Measurement range - 0...20 mA - Current input: Programmable measurement ranges - 0...20 and 4...20 mA - Input resistance, current input - Nom. 20 Ω + PTC 50 Ω - Voltage input: Measurement range - 0...12 VDC - Programmable measurement ranges, VDC - 0/0.2...1, 0/1...5, 0/2...10 VDC - Input resistance, voltage input - Nom. 10 MΩ - Output specifications- Current output: Signal range - 0...20 mA - Programmable current ranges - 0...20 / 4...20 / 20...0 and 20...4 mA - Load (max.) - 20 mA/800 Ω/16 VDC - Load stability, current output - ≤0.01% of span / 100 Ω - Sensor error indication, current output - 0 / 3.5 / 23 mA / none - NAMUR NE 43 Upscale/Downscale - 23 mA / 3.5 mA - Current limit - ≤ 28 mA - Voltage output: signal range - 0...10 VDC - Programmable voltage ranges - 0/0.2...1; 0/1...5 ; 0/2...10; 1...0.2/0; 5...1/0; 10...2/0 V - Load (min.) - 500 kΩ - *of span - = of the currently selected measurement range - Approvals- EMC - EN 61326-1 - LVD 2006/95/EC - EN 61010-1 - FM - 3025177 - UL - UL 508 - EAC TR-CU 020/2011 - EN 61326-1 - DNV Marine - Stand. f. Certific. No. 2.4 - SIL - Hardware assessed for use in SIL applications 


 
  
 