- Advanced features- Programmable via detachable display front (4501), process calibration, relay simulation, password protection, error diagnostics and selection of help text in several languages.
 - Application- Process control with 2 pairs of potential-free relay contacts which can be configured to suit any application.
- Trip amplifier with window function defined by a high and a low setpoint. The relay changes state outside the window.
- Relay latch function, where the relay is activated and can only be reset manually.
- Sophisticated sensor error surveillance, where one relay holds the state immediately prior to the sensor error, while allowing the process to continue. The other relay can be set for sensor error alarm so that the defect sensor can be replaced immediately.
 - Technical characteristics- When 4131 is used with the 4501 display / programming front, all operational parameters can be modified to suit any application. As the 4131 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
- Continuous check of vital stored data for safety reasons.
- 3-port 2.3 kVAC galvanic isolation.
 
- Environmental Conditions- Specifications range - -20°C to +60°C - Calibration temperature - 20...28°C - Relative humidity - < 95% RH (non-cond.) - Protection degree - IP20 - Mechanical specifications- Dimensions (HxWxD) - 109 x 23.5 x 104 mm - Dimensions (HxWxD) w/ 4501 / 4511 - 109 x 23.5 x 116 / 131 mm - Weight approx. - 170 g - Weight incl. 4501 / 4511 (approx.) - 185 g / 270 g - Wire size - 1 x 2.5 mm2 stranded wire - Screw terminal torque - 0.5 Nm - Vibration: 2...13.2 Hz - ±1 mm - Vibration: 13.2...100 Hz - ±0.7 g - Common specifications- Supply voltage, universal - 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC - Fuse - 400 mA SB / 250 VAC - Max. power consumption - ≤ 2.0 W - Isolation voltage, test / working - 2.3 kVAC / 250 VAC - Communications interface - Communication enabler 4511 / Programming front 4501 - Signal / noise ratio - Min. 60 dB (0...100 kHz) - Response time (0...90%, 100...10%): Temperature input - ≤ 1 s - Response time (0...90%, 100...10%): mA / V input - ≤ 400 ms - Accuracy - Better than 0.1% of selected range - Auxiliary supplies: 2-wire supply (terminal 44...43) - 25...16 VDC / 0...20 mA - EMC immunity influence - < ±0.5% of span - Extended EMC immunity: NAMUR NE 21, A criterion, burst - < ±1% of span - Input specifications- RTD input - Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000 Ni50, Ni100, Ni120, Ni1000, Cu10, Cu20, Cu50, Cu100 Linear resistance 
 Potentiometer- Cable resistance per wire (max.), RTD - 50 Ω - Sensor current, RTD - Nom. 0.2 mA - Effect of sensor cable resistance (3-/4-wire), RTD - < 0.002 Ω / Ω - Sensor error detection, RTD - Yes - Short circuit detection, RTD - < 15 Ω - TC input: Thermocouple type - B, E, J, K, L, N, R, S, T, U, W3, W5, LR - Cold junction compensation (CJC) via ext. sensor in connector 5910 - 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C - CJC via internally mounted sensor - ±(2.0°C + 0.4°C * Δt) - Δt = - Internal temperature-ambient temperature - Sensor error detection, TC - Yes - Sensor error current: When detecting / else - Nom. 2 μA / 0 μA - Current input: Measurement range - 0...20 mA - Current input: Programmable measurement ranges - 0...20 and 4...20 mA - Input resistance, current input - Nom. 20 Ω + PTC 50 Ω - Voltage input: Measurement range - 0...12 VDC - Programmable measurement ranges, VDC - 0/0.2...1, 0/1...5, 0/2...10 VDC - Input resistance, voltage input - Nom. 10 MΩ - Output specifications- Relay output: Relay functions - Setpoint, Window, Sensor error, Latch, Power and Off - Hysteresis - 0...100% - ON and OFF delay - 0...3600 s - Max. voltage - 250 VRMS - Max. current - 2 AAC or 1 ADC - Max. AC power - 500 VA - Sensor error reaction - Break / Make / Hold - *of span - = of the currently selected measurement range - Approvals- EMC - EN 61326-1 - LVD 2006/95/EC - EN 61010-1 - FM - 3025177 - UL - UL 508 - EAC TR-CU 020/2011 - EN 61326-1 - DNV Marine - Stand. f. Certific. No. 2.4 


 
  
 


