- Advanced features- The 5114 transmitter can be configured, with or without a power supply, using the PReset software and the Loop Link communications unit.
 - Application- Jumper selectable inputs for current/voltage or temperature.
- Programmable current (0...100 mA) and voltage (0...250 VDC) inputs.
- Linearized, electronic temperature measurement.
- Conversion of linear resistance variation e.g, from solenoids and butterfly valves or linear movements with attached potentiometer.
- 17.1 VDC loop and 2.5 VDC potentiometer supplies.
- Automatic 4- / 3-wire or programmable 2-wire cable compensation.
- Configurable sensor error detection including NAMUR NE43.
 - Technical characteristics- Active or Passive current output and selectable voltage output.
- Separation of circuits in PELV/SELV installations.
 
- Environmental Conditions- Specifications range - -20°C to +60°C - Calibration temperature - 20...28°C - Relative humidity - < 95% RH (non-cond.) - Protection degree - IP20 - Mechanical specifications- Dimensions (HxWxD) - 109 x 23.5 x 130 mm - Weight approx. - 225 g - DIN rail type - DIN 46277 - Wire size - 1 x 2.5 mm2 stranded wire - Screw terminal torque - 0.5 Nm - Common specifications- Supply voltage, universal - 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC - Fuse - 400 mA SB / 250 VAC - Max. power consumption - ≤ 3 W (2 channels) - Internal consumption - ≤ 2 W (2 channels) - Isolation voltage, test / working - 3.75 kVAC / 250 VAC - Communications interface - Loop Link - Signal / noise ratio - Min. 60 dB (0...100 kHz) - Response time (0...90%, 100...10%): Temperature input (programmable) - 400 ms...60 s - mA / V input (programmable) - 250 ms...60 s - Updating time - 115 ms (temperature input) 75 ms (mA / V / mV input) - Signal dynamics, input - 22 bit - Signal dynamics, output - 16 bit - Auxiliary voltages: Reference voltage - 2.5 VDC ±0.5% / 15 mA - Auxiliary supply: 2-wire supply (pin 44...42 and 54...52) - 28...17.1 VDC / 0...20 mA - EMC immunity influence - < ±0.5% of span - Extended EMC immunity: NAMUR NE 21, A criterion, burst - < ±1% of span - Input specifications- Max. offset - 50% of selected max. value - RTD input - Pt100, Ni100, lin. R - Cable resistance per wire (max.), RTD - 10 Ω - Sensor current, RTD - Nom. 0.2 mA - Effect of sensor cable resistance (3-/4-wire), RTD - < 0.002 Ω / Ω - Sensor error detection, RTD - Yes - TC input: Thermocouple type - B, E, J, K, L, N, R, S, T, U, W3, W5, LR - Cold junction compensation (CJC) - < ±1.0°C - Sensor error current, TC - Nom. 30 μA - Sensor error detection, TC - Yes - Current input: Measurement range - 0...100 mA - Min. measurement range (span), current input - 4 mA - Input resistance: Supplied unit - Nom. 10 Ω + PTC 10 Ω - Input resistance: Non-supplied unit - RSHUNT = ∞, VDROP < 6 V - Voltage input: Measurement range - 0...250 VDC -150...+150 mV - Min. measurement range (span), voltage input - 5 mV - Input resistance, voltage input - Nom. 10 MΩ (≤ 2.5 VDC) Nom. 5 MΩ (> 2.5 VDC) 
 Nom. 10 MΩ (mV input)- Output specifications- Max. offset - 50% of selected max. value - Current output: Signal range - 0...20 mA - Min. signal range - 10 mA - Load (max.) - 20 mA/600 Ω/12 VDC - Load stability, current output - ≤0.01% of span / 100 Ω - Current limit - ≤ 28 mA - 2-wire 4...20 mA output: Signal range - 4...20 mA - Load stability, 4…20 mA output - ≤ 0.01% of span / 100 Ω - Max. load resistance [Ω] - (Vsupply - 3.5) / 0.023 A - Max. external 2-wire supply - 29 VDC - Effect of external 2-wire supply voltage variation - < 0.005% of span / V - Voltage output: signal range - 0...10 VDC - Voltage output, min. signal range - 500 mV - Load (min.) - 500 kΩ - Sensor error indication, current output - Programmable 0...23 mA - NAMUR NE 43 Upscale/Downscale - 23 mA / 3.5 mA - *of span - = of the presently selected range - Approvals- EMC - EN 61326-1 - LVD 2006/95/EC - EN 61010-1 - PELV/SELV - IEC 364-4-41 and EN 60742 - EAC TR-CU 020/2011 - EN 61326-1 - DNV Marine - Stand. f. Certific. No. 2.4 


 
  
 