- Application and advanced features- The power control unit detects errors from any of the devices mounted on the power rail and transmits a collective alarm to the control system via the internal status relay.
- Optional connection of two power supplies - a primary supply and a backup supply.
- Redundant supply for the power rail can be obtained by mounting two 9410 devices connected to 2 separate power supplies (e.g. PR 9420).
 - Technical characteristics- The status relay will be energised when the following three conditions are met:
 1. Supply voltage is present on pins 31 and 32.
 2. Backup supply voltage is present on pins 34 and 33. (If the backup supply is not in use, a jumper must be placed between pins 32 and 33 - the jumper is delivered with the device).
 3. There are no error messages from the devices connected to the power rail.
- When a collective alarm is activated via the power rail, the status relay in the 9410 will be de-energized (pins 11, 12 and 13).
- Two green front LEDs indicate connection of supply and backup.
- A red LED indicates error status.
 
- Environmental Conditions- Specifications range - -20°C to +60°C - Storage temperature - -20°C to +85°C - Relative humidity - < 95% RH (non-cond.) - Protection degree - IP20 - Mechanical specifications- Dimensions (HxWxD) - 109 x 23.5 x 104 mm - Weight approx. - 140 g - Wire size - 0.13...2.08 mm2AWG 26...14 stranded wire - Screw terminal torque - 0.5 Nm - Common specifications- Max. power consumption - 96 W - Internal consumption - 2 W (max.) - Efficiency - > 97.9% - Input specifications- Supply voltage - 21.6...26.4 VDC (double / reinforced isolation) - Backup supply - 21.6...26.4 VDC - Output specifications- Output voltage - Input voltage-0.5 VDC (@ 4 A) - Output power - 96 W (max.) - Output current - 4 A (max.) - Output ripple - Same as input ripple - Max. voltage, status relay - 250 / 30 VDC - Max. current, status relay - 2 AAC / 2 ADC - Max. AC power, status relay - 500 VA / 60 W - Approvals- EMC - EN 61326-1 - LVD 2006/95/EC - EN 61010-1 - ATEX 2004/108/EC - KEMA 07ATEX0152 X - IECEx - KEM 08.0025X - FM - 3034431-C - INMETRO - NCC 12.1308 X - UL - UL 61010-1 - EAC TR-CU 020/2011 - EN 61326-1 - DNV Marine - Stand. f. Certific. No. 2.4 


 
  
 