- Advanced features- The 5131A transmitter can be configured with the software program PReset using a standard PC and the Loop Link communications unit.
 - Application- Independent channel jumper selectable inputs for current/voltage or temperature.
- Current input programmable in range 0...100 mA and voltage inputs in range 0...250 VDC.
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, for example from solenoids and butterfly valves or linear movements with attached potentiometer.
- 4- or 3-wire connection automatic cable compensation or 2-wire connection with programmable cable compensation.
- Configurable sensor error detection including NAMUR NE43.
 - Technical characteristics- Analog current output can be configured to any current within 0...20 mA range.
- Voltage output range is selectable between 0...10 VDC.
- Programming can be performed with or without a power supply.
- The 2-channel version has full galvanic isolation between the channels.
- Separation of circuits in PELV/SELV installations.
 
- Environmental Conditions- Specifications range - -20°C to +60°C - Calibration temperature - 20...28°C - Relative humidity - < 95% RH (non-cond.) - Protection degree - IP20 - Mechanical specifications- Dimensions (HxWxD) - 109 x 23.5 x 130 mm - Weight approx. - 195 g - DIN rail type - DIN 46277 - Wire size - 1 x 2.5 mm2 stranded wire - Screw terminal torque - 0.5 Nm - Common specifications- Supply voltage - 7.5...35 VDC - Fuse - 50 mA SB / 250 VAC - Isolation voltage, test / working - 3.75 kVAC / 250 VAC - Communications interface - Loop Link - Signal / noise ratio - Min. 60 dB (0...100 kHz) - Signal dynamics, input - 22 bit - Signal dynamics, output - 16 bit - Updating time - 115 ms (temperature input) 75 ms (mA / V / mV input) - Response time (0...90%, 100...10%): Temperature input (programmable) - 400 ms...60 s - mA / V input (programmable) - 250 ms...60 s - EMC immunity influence - < ±0.5% of span - Extended EMC immunity: NAMUR NE 21, A criterion, burst - < ±1% of span - Effect of supply voltage change - < 0.005% of span / VDC - Input specifications- Max. offset - 50% of selected max. value - RTD input - Pt100, Ni100, lin. R - Cable resistance per wire (max.), RTD - 10 Ω - Sensor current, RTD - Nom. 0.2 mA - Effect of sensor cable resistance (3-/4-wire), RTD - < 0.002 Ω / Ω - Sensor error detection, RTD - Yes - TC input: Thermocouple type - B, E, J, K, L, N, R, S, T, U, W3, W5, LR - Cold junction compensation (CJC) - < ±1.0°C - Sensor error current, TC - Nom. 30 μA - Sensor error detection, TC - Yes - Current input: Measurement range - 0...100 mA - Min. measurement range (span), current input - 4 mA - Input resistance: Supplied unit - Nom. 10 Ω + PTC 10 Ω - Input resistance: Non-supplied unit - RSHUNT = ∞, VDROP < 6 V - Voltage input: Measurement range - -150...+150 mV 0...250 VDC - Min. measurement range (span), voltage input - 5 mV - Input resistance, voltage input - Nom. 10 MΩ (≤ 2.5 VDC) Nom. 5 MΩ (> 2.5 VDC) - Output specifications- Max. offset - 50% of selected max. value - Current output: Signal range - 4…20 mA - Min. signal range - 10 mA - Load resistance, current output - ≤ (Vsupply -7.5)/0.023 [Ω] - Load stability, current output - ≤0.01% of span / 100 Ω - Current limit - ≤ 28 mA - Sensor error indication, current output - Programmable 3.5…23 mA - NAMUR NE 43 Upscale/Downscale - 23 mA / 3.5 mA - *of span - = of the presently selected range - Approvals- EMC - EN 61326-1 - LVD 2006/95/EC - EN 61010-1 - PELV/SELV - IEC 364-4-41 and EN 60742 - ATEX 2004/108/EC - DEMKO 99ATEX124572 


 
  
 