5337A
2-wire transmitter with HART® protocol
- RTD, TC, Ohm, and bipolar mV input
- 2 analogue inputs and 5 device variables with status available
- HART® protocol revision selectable from HART® 5 or HART® 7
- Hardware assessed for use in SIL applications
- Mounting in Safe area or Zone 2/22
Manuals : 
Data sheet : 
Application
- Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
- HART® communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
- Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
- Amplification of bipolar mV signals to standard 4...20 mA current signals.
- Up to 63 transmitters (HART® 7) can be connected in a multidrop communication setup.
Technical characteristics
- HART® protocol revision can be changed by user configuration to either HART® 5 or HART® 7 protocol.
- The HART® 7 protocol offers:
∙ Long Tag numbers of up to 32 characters.
∙ Enhanced Burst Mode and Event notification with time stamping.
∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
∙ Process signal trend measurement with logs and summary data.
∙ Automatic event notification with time stamps.
∙ Command aggregation for higher communication efficiency. - 5337A is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
- Continuous check of vital stored data.
- Meeting the NAMUR NE21 recommendations, the 5337 HART® transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337 meets NAMUR NE43 and NE89 recommendations.
Mounting / installation
- For DIN form B sensor head or DIN rail mounting via the PR fitting type 8421.
- Configuration via standard HART® communication interfaces or by PR 5909 Loop Link.
Environmental Conditions
Specifications range -40°C to +85°C Calibration temperature 20...28°C Relative humidity < 95% RH (non-cond.) Protection degree (encl./terminal) IP68 / IP00 Mechanical specifications
Dimensions Ø 44 x 20.2 mm Weight approx. 50 g Wire size 1 x 1.5 mm2 stranded wire Screw terminal torque 0.4 Nm Vibration IEC 60068-2-6 : 2007 Vibration: 2...25 Hz ±1.6 mm Vibration: 25...100 Hz ±4 g Common specifications
Supply voltage 8.0...35 VDC Voltage drop 8.0 VDC Isolation voltage, test / working 1.5 kVAC / 50 VAC Signal / noise ratio > 60 dB Communications interface Loop Link & HART® Response time (programmable) 1...60 s Accuracy Better than 0.05% of selected range EMC immunity influence < ±0.1% of span Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span Input specifications
Max. offset 50% of selected max. value RTD input Pt50, Pt100, Pt200, Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000 Cable resistance per wire (max.), RTD 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy) Sensor current, RTD Nom. 0.2 mA TC input: Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR Cold junction compensation (CJC) Constant, internal or external via a Pt100 or Ni100 sensor Voltage input: Measurement range -800...+800 mV Min. measurement range (span), voltage input 2.5 mV Input resistance, voltage input 10 MΩ Output specifications
Current output: Signal range 4…20 mA Min. signal range 16 mA Updating time 440 ms Load resistance, current output ≤ (Vsupply - 8) / 0.023 [Ω] Sensor error indication, current output Programmable 3.5…23 mA NAMUR NE 43 Upscale/Downscale 23 mA / 3.5 mA HART protocol revisions HART 5 and HART 7 Approvals
EMC EN 61326-1 ATEX 2004/108/EC KEMA 03ATEX1508 X IECEx KEM 10.0083X INMETRO NCC 12.0844 X EAC TR-CU 020/2011 EN 61326-1 DNV Marine Stand. f. Certific. No. 2.4 SIL Hardware assessed for use in SIL applications